Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) FINAL AFTER CORRECTIONS 5 & 6 |
|
| 06/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FINISH PREVIOUS ITEMS: 1) #5 ALL KITCHEN RECEPTS 210.8 2) #8 CANNOT USE SHEET METAL THREAD SCREWS 250.8 3) #10 PLEASE PROVIDE PAPERWORK FOR REVISION AND BOND GEC TO EQG 4) #11 EM LIGHTING TO BE PER 700.12 (F) 5) #1 ROOF-SUPPORT CONDUITS AND SEAL TIGHT 6) #6 NEED ARC SHIELDS 314.20 |
|
| 04/06/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |