Permit: T08CM00822

Parcel: 13628005Q


Addresses:

7810 E ESCALANTE RD

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
05/19/2008 FIRE - FINAL Approved
03/31/2008 FIRE - FINAL Denied Need to correct sprinkler coverage in Infoxx hallway. Head is 12' off wall.
03/26/2008 FIRE - FINAL Not ready for Inspection Need up to date fire sprinkler inspection done, this is done yearly last on file 8/07/03.
Need up to date fire alarm check valve inspection, this is done every 5 years last on file 4/05/2002.
Need approved plans on site at all times.