Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PLAN CALLS FOR 100 AMP BREAKER NEW PANEL 2) NEED TO REVISE PLAN OR LABEL PLAN ON HOW WIRING IS TO BE DONE, THINGS HAVE BEEN CHANGED FEWER LIGHT FIXTURES MORE CIRCUITS CALCULATED LOAD FOR NEW PANEL 3) HOME RUN FEEDER NOT INSTALLED YET 4) NEED NAIL PROTECTION THRU OUT FOR ALL WIRES CLOSER THAN 1 1/4" FROM EDGE OF 2 X |
|
| 06/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |