Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T08CM00815
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2009 | FRAMING | Approved | IVRS - Inspection :* | |
06/22/2009 | FRAMING | Partial Approval | IVRS - Inspection :* INTERIOR FRAMING AND GRAB BAR BLOCKING EXTERIOR CLIPS (H2.5's) AND TAPCONS NEED LETTER FROM ARCH. RE:INTERIOR METAL STUD SOFFIT |
|
06/02/2008 | FRAMING | Partial Approval | IVRS - Inspection :* NEEDS SIMPSONS S1-6 SHEAR WALL BLOCKING 1. NEEDS ELEC & PLUMBING INTERMEDIATE BEFORE ROCKING 2. TOILET FLUSH LEVER NEEDS TO BE ON OPEN SIDE |
|
05/19/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DETAILS (1) BACKING FOR ADA GRAB BARS A4 2. CENTER OF 16" TO 18" FROM WALL A4 3. SIMPSONS S1 (4) 4. S1 DETAIL (3) 4 3/4" BOLTS 5. S2 (3) 6. S1 (2) 7. G ON S2 |
|
05/09/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO PLANS NO PERMIT NO ONE AT SITE |