Permit: T08CM00814

Parcel: 10409002D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM00814

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/03/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/02/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ALL CORRECTIONS BEFORE CALLING IN
07/01/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
DOOR LOCKED @ 12:30 PM
06/26/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PREVIOUS CORRECTIONS NOT COMPLETED
2. CHECK CEILINGS ABOVE BATHROOMS & CLOSET
06/24/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
1. SUPPORT WIRE NEEDED ON FIXTURES
2. USE APPROVED STRAPS
3. FILL UNUSED OPENINGS IN BOXES

PLEASE PAY REFEE BEFORE NEXT INSPECTION
06/20/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRING NOT PER PLAN
2. MC TO BE SECURED WITHIN 12" OF TERMINATIONS
AND MAX. 6' INTERVALS
3. MC NOT TO LAY ON GRID OR OTHER EQUIPMENT
4. DO NOT USE GRID SUPPORT WIRES TO SUPPORT EQUIPMENT
5. INDIVIDUAL SUPPORT WIRES TO BE SECURED AT BOTH ENDS
6. HAVE OVERFILLED J-BOXES
7. HAVE IMPROPERLY GROUNDED J-BOXES - SELF TAP SCREWS NOT ALLOWED
8. MC TO TERMINATE WITH PROPER CONNECTOR - NOT JUST PUSHED DOWN EMT

PARTIAL INSPECTION - GO THROUGH ALL WORK AND BRING TO CODE - VERY SLOPPY
06/19/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/18/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CEILING TILES INSTALLED BEFORE APPROVAL TO BE REMOVED
2. DO NOT CALL BEFORE ELECTRICIANS ARE COMPLETE AND THEY TELL YOU THEY ARE READY FOR INSPECTION