Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/19/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. HAVE OVERFILLED J-BOXES (NEC 314.16) 2. HAVE OVERFILLED WIRENUTS (NEC 110.3B) CORRECT AS NEEDED OK CEILING TILES PHASE 1 AFTER THAT 3. TEMP POWER TO TRAILERS TO BE PERMITTED AND INSPECTED - REMOVE AND DE-ENERGIZE ILLEGAL FEED TO TRAILERS. |