Permit: T08CM00807

Parcel: 12112390B


Addresses:

5240 E PIMA ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/25/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/22/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 3/8" I.D X 18" GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE
2. SEAL HOLD IN SIDE OF EXPOSED DUCT ON ROOF
3. SUPPORT ALL ELEC. CONDUIT ON ROOF
4. TIGHTEN LOOSE FITTINGS
5. SEAL FRESH AIR INTAKE CONNECTION TO DUCT ON ROOF
6. FINISH WATER HEATER VENT ON ROOF
7. PROVIDE SHIELDS OVER CANVAS CONNECTORS ON
EXISTING AC UNIT
8. SUPPORT DUCT ON ROOF AT FLEX CONNECTOR
EXISTING UNIT.
9. LEVEL THE EXISTING AC UNIT
10. TURN THE SLEEPERS ON NEW AC UNITS TO
SPAN ROOF JOISTS
11. I.D UNITS ON ROOF
12. PROVIDE AIR BALANCE REPORT
13. PROVIDE AN ELBOW AT CONDENSATE TERMINATION
14. SLOPE CONDENSATE MIN. 1/8" PER FT.