Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RECEIVED LETTER FOR CHANGE IN SWITCHING OK FINAL |
|
| 08/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MARK SERVICE DISCONNECTS "SERVICE DISCONNECT 1 OF 2" "SERVICE DISCONNECT 2 OF 2" 2. INSTALL BOX EXTENSIONS ON RECEPTACLES & SWITCHES IN RESTROOMS 3. DISHWASHER CORD TO BE BETWEEN 36" & 48" 4. EM LIGHTING TO BE CONNECTED TO CIRCUIT IN AREA SEE PLAN 5. SWITCHING OF LIGHT FIXTURES NOT PER PLAN |
|
| 08/22/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE SPACE VERIFY POWER AND ALL LIGHTING IS WORKING 2. MOVE ALL FURNITURE AWAY FROM WALLS TO HAVE ACCESS TO RECEPTACLES. SPACE NOT TO BE OCCUPIED UNTIL FINAL INSPECTIONS COMPLETED |