Permit: T08CM00807

Parcel: 12112390B


Addresses:

5240 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/26/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
RECEIVED LETTER FOR CHANGE IN SWITCHING

OK FINAL
08/25/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MARK SERVICE DISCONNECTS
"SERVICE DISCONNECT 1 OF 2" "SERVICE DISCONNECT 2 OF 2"
2. INSTALL BOX EXTENSIONS ON RECEPTACLES & SWITCHES IN RESTROOMS
3. DISHWASHER CORD TO BE BETWEEN 36" & 48"
4. EM LIGHTING TO BE CONNECTED TO CIRCUIT IN
AREA SEE PLAN
5. SWITCHING OF LIGHT FIXTURES NOT PER PLAN
08/22/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE SPACE VERIFY POWER AND ALL LIGHTING IS WORKING
2. MOVE ALL FURNITURE AWAY FROM WALLS TO HAVE ACCESS TO RECEPTACLES. SPACE NOT TO BE OCCUPIED UNTIL FINAL INSPECTIONS COMPLETED