Permit: T08CM00793

Parcel: 110113630


Addresses:

2460 N SWAN RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/09/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/08/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE MIN R8 DUCT LINER IN EXPOSED DUCT ON ROOF.
INCLUDE PLENUMS INSIDE CURB ADAPTORS
PAINT EXPOSED PVC W/LATEX PAINT
MARK UNIT DATA PLATES WITH PROPER HEAT STRIP
INSTALLED & FUSE ACCORDINGLY
PERMANENTLY I.D EQUIPMENT. NO INK.
07/01/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE PROPER FUSES
2. PAINT ALL PVC
3. PAINT ALL EXPOSED DUCT WITH WHITE ELASTIOMERIC PAINT
4. SET ALL OSA AT 2/3 OPEN