Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00782

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/12/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/29/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
BUILDING INSPECTOR TO VERIFY ARC SHIELDS AT FLUORESCENTS
08/27/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
USE APPROVED EXTENDER RINGS AT COMBUSTIBLES 314.20
08/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
* AREA OCCUPIED WITHOUT FINAL INSPECTIONS

1. PLEASE PROVIDE LADDERS TO INSPECT ROOF AND LIGHTS
2. CIRCUIT DIRECTORY TO BE AS PER 408.4 NO ABBREVIATION AND LEGIBLE - ALSO LABEL OUTSIDE OF COVER
3. CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL
4. FEEDERS AND PANEL (MAIN BREAKER) NOT AS PER PLANS