Permit: T08CM00779

Parcel: 11003081D

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
11/06/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
10/01/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROVIDE A CONDENSATE DRAIN FOR FAN COIL IN
SERVER ROOM
2. LABEL ALL FAN COILS
3. PROVIDE BUSHINGS AT REFER LINE CONNECTIONS
TO FAN COILS
4. PROVIDE CRADLES FOR FLEX DUCTS AS PER PLAN
07/23/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*