Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/07/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* ENSURE BREAKERS IN PANELS MEET AIC RATING PER PLANS |
|
| 08/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK INSIDE STAIRWELL ROUGH |
|
| 08/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SOFFITS LTG. 1ST, 2ND FLOOR OK RESTROOMS, HARD LIDS - 2ND FLOOR OK HARD LIDS LOBBY, HALLWAY - 1ST FLOOR |
|
| 07/01/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1ST FLOOR WALLS |
|
| 06/27/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CORRECTIONS NOT COMPLETED NAIL PLATES ARE REQUIRED WHERE HOLE IS LESS THAN 1 1/4 FROM STUD FACE |
|
| 06/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS 2ND FLOOR |
|
| 06/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. STRAP MC WITHIN 12" OF BOXES 2. PROTECT MC AT STUDS 300.4 3. PROTECT RACEWAYS FOR VDV CABLING FROM SHARP METAL EDGES 4. FINISH STAIRWELL WALLS 5. PLANS CALL FOR 3/4" CONDUIT - NEED LETTERS OK ONE SIDE 1ST FLOOR |