Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/12/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/11/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* AC-3 AND AC-4 ARE NOT PER PLAN AND DO NOT FALL WITHIN BALANCE PARAMETERS REPLACE WITH UNIT MODEL INDICATED ON EQUIPMENT SCHEDULE EF-1 AND EF-2 ARE NOT THE CORRECT SIZE FANS PROVIDE PROPER FANS AND ALUM GRILL SUPPLIED BY MANUFACTURER PER EXHAUST FAN SCHEDULE NOTE (4) PLEASE REFER TO MECHANICAL NOTES 1.03, 1.05, 1.06, 2.01 |
|
| 08/08/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE AIR BALANCE REPORT |