Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT J-BOXES TO STRUCTURE ON EAST WALL. PLUG UNUSED OPENING 2. SEISMIC WIRES USED FOR SUPPORT MUST BE TIED OFF AT BOTH ENDS, USE APPROVED SUPPORT HARDWARE. 3. MC MUST BE SUPPORTED PER CODE, 12" AND AT 6' INTERVALS |
|
| 06/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROUGH |