Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/10/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) ENGINEER REPORT HAS TO HAVE CITY STAMP OF APPROVAL 2) NEED SIGNATURE FROM PERSON DOING INSPECTION |
|
| 05/16/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PARTIAL UNTIL SLAB HAS BEEN REPAIRED IN BATHROOM WITH PROPER 3RD PARTY INSPECTIONS |
|
| 05/14/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DBL STUDS AT DBL GIRDERS 2) NEED TO BLOCK HIGH/LOW COMBUSTION AIR-GARAGE 3) NO DWV TEST 4) PROTECT PLATE FOR WIRING-LAUNDRY ROOM TOP PLATE DRY EXHAUST VENT 5) 1 X IN CEILING KITCHEN NORTHWALL 6) FIRESEAL ALL PENETRATIONS IN TOP PLATES NOT USED (KITCHEN BY RANGE VENT) 7) FIX STUD ADJACENT TO MASTER BATH AND BEDROOM 8) NEED ENGINEERED FIX FOR CUT SLABG AT MASTER BATH TAPE ALL NICKS INTENDONS 9) SHIM ALL HEADERS 10) SEAL AROUND ALL WINDOWS 11) STOPPED INSPECTION |