Permit: T08CM00764

Parcel: 10603014A


Addresses:

104 E PRINCE RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM00764

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/06/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/04/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/12/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) HAVE ENGINEER REVIEW AND COMMENT ON BALANCE REPORT PRIOR TO NEXT INSPECTION
10/13/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE AIR BALANCE REPORT
2. PROVIDE ISOLATORS UNDER CONDENSOR UNITS PER DETAILS
3. ISOLATE COPPER REFRIGERATION LINES FROM GALVANIZED