Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T08CM00764
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/27/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE FLEX CONNECTORS PER DETAIL 102 2. PROVIDE CONICAL TAPS PER DETAIL 107 3. SUPPORT ON FLEX DUCT NOT TO EXCEED 5' 4. PAINT INSIDE ALL GRILLS BLACK WHERE VISIBLE 5. INSULATE ALL SHEETMETAL DUCTING NOT LINED 6. PROVIDE SPRING ISOLATORS AT ALL UNITS PER DETAIL 102 7. PROVIDE CLEANOUTS IN CONDENSATE |