Permit: T08CM00764

Parcel: 10603014A


Addresses:

104 E PRINCE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00764

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/06/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. IDENTIFY DATA PLATE TO VERIFY CORRECT SIZED FUSES AND FUSE ACCORDINGLY
2. FINISH MAINTAINING WORKING CLEARANCES
11/07/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. MAINTAIN WORKING CLEARANCE AT A/C DISCONNECT
2. FAN COIL CONDUCTOR TO SMALL FOR LOAD
3. FINISH #2 OLD INSPECTIONS
11/06/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
10/31/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. USE TERMINAL ENDS WITH STRANDED CONDUCTORS UNDER SCREWS
2. EXTERIOR LIGHTS NOT AS PER PLANS #9 PREVIOUS
3. OPEN TILES ALL AROUND LIGHTS TO INSPECT #5 PREVIOUS
10/13/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CLEAN EXCESS FOREIGN MATERIAL FROM PANEL 110.12
2. LABEL CIRCUITS AS PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER - ALSO, LABEL OUTSIDE OF PANEL COVER
3. VERIFY DERATING PER 310.15
4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
5. PLEASE REMOVE TILES TO INSPECT ABOVE CEILING
6. GROUNDED CONDUCTOR TO BE WHITE ENTIRE
LENGTH 200.7 IN RACEWAY
7. INSTALL WATER HEATER
8. MAINTAIN WORKING CLEARANCES AT A/C DISCONNECTS 110.26
9. EXTERIOR LIGHTS TO BE FULL CUT OFF AS PER PLANS
10. LABEL DISCONNECTING MEANS
11. BOND DISCONNECT ENCLOSURES