Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00764
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/06/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. IDENTIFY DATA PLATE TO VERIFY CORRECT SIZED FUSES AND FUSE ACCORDINGLY 2. FINISH MAINTAINING WORKING CLEARANCES |
|
| 11/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCE AT A/C DISCONNECT 2. FAN COIL CONDUCTOR TO SMALL FOR LOAD 3. FINISH #2 OLD INSPECTIONS |
|
| 11/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 10/31/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. USE TERMINAL ENDS WITH STRANDED CONDUCTORS UNDER SCREWS 2. EXTERIOR LIGHTS NOT AS PER PLANS #9 PREVIOUS 3. OPEN TILES ALL AROUND LIGHTS TO INSPECT #5 PREVIOUS |
|
| 10/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CLEAN EXCESS FOREIGN MATERIAL FROM PANEL 110.12 2. LABEL CIRCUITS AS PER 408.4 - NO ABBREVIATIONS AND DISTINGUISHABLE FROM ONE ANOTHER - ALSO, LABEL OUTSIDE OF PANEL COVER 3. VERIFY DERATING PER 310.15 4. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20 5. PLEASE REMOVE TILES TO INSPECT ABOVE CEILING 6. GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH 200.7 IN RACEWAY 7. INSTALL WATER HEATER 8. MAINTAIN WORKING CLEARANCES AT A/C DISCONNECTS 110.26 9. EXTERIOR LIGHTS TO BE FULL CUT OFF AS PER PLANS 10. LABEL DISCONNECTING MEANS 11. BOND DISCONNECT ENCLOSURES |