Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T08CM00764
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/22/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER BONDING AT SERVICE TO COMPLY WITH 250-104 2) USE PROPER CLAMP AT RISER BRACE 3) LOADS NOT INSTALLED YET |
|
| 05/21/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING CONDUCTORS AT SERVICE TO COMPLY WITH 250.6 NEC 2. UNCOVER GROUND RODS, METAL RACEWAYS FOR GROUNDING ELECTRODE CONDUCTORS TO COMPLY WITH 250.64E 3. REMOVE ALL COVERS FOR INSPECTION 4. VERIFY WATER & GAS BONDING |