Permit: T08CM00754

Parcel: 14111031A

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
06/17/2008 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
06/16/2008 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1. TIGHTEN "C" PHASE TERMINATION
2. PLEASE ADD #120 TO PERMIT
06/13/2008 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
06/12/2008 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLAN CALLS FOR ALL CONDUCTORS TO BE COPPER
2. INSTALL PROTECTIVE BUSHING ON CONNECTIONS WHERE CONDUCTORS LARGER THAN #4
3. BOND METER ENCLOSURE
4. INSTALL NEUTRAL BAR PROPERLY IN DISCONNECTS
5. MARK "SERVICE DISCONNECTS"