Permit: T08CM00753

Parcel: 128100540

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM00753

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/19/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
06/13/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EF-1 NOT THE FAN REQUIRED ON PLANS
2. DUCT TO EXHAUST FAN NOT SIZED PER PLAN
3. PROVIDE A HOSE CLAMP WHERE PLASTIC CONDENSATE HOSE CONNECTS TO BRASS FITTING
4. PROVIDE A DUCT SMOKE DETECTOR FOR FIRE/SMOKE DAMPER AS PER SECTION 607.3.2.1 2006 IMC
5. FIRE/SMOKE DAMPER DOES NOT HAVE POWER RAN TO IT AND IS CLOSED AT THIS TIME
05/22/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*