Permit: T08CM00753

Parcel: 128100540

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
04/09/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
- FIRE/SMOKE DAMPER REQUIRES A DUCT SMOKE DETECTOR WITHIN 5' OF DAMPER.
- ALL DAMPERS REQUIRE ACCESS DOORS.
- WILL CHECK ON FINAL.
- ALSO, NEED TO SEE NEW AC UNIT & CONDENSATE
DRAIN LINE
- FIRE/SMOKE DAMPER MISSING ANGLE IRON ONE SIDE
- OK CEILING TILES