Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* - FIRE/SMOKE DAMPER REQUIRES A DUCT SMOKE DETECTOR WITHIN 5' OF DAMPER. - ALL DAMPERS REQUIRE ACCESS DOORS. - WILL CHECK ON FINAL. - ALSO, NEED TO SEE NEW AC UNIT & CONDENSATE DRAIN LINE - FIRE/SMOKE DAMPER MISSING ANGLE IRON ONE SIDE - OK CEILING TILES |