Permit: T08CM00753

Parcel: 128100540

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/15/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL

RECEIVED LETTER FROM ENGINEER FOR CHANGE IN FEEDER TO AETNA PANEL
04/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUB-PANEL NOT PER PLAN. IN GROUND TO GO TO POINT OF XO AT XFMR - IN GROUND TO BE RUN IN RACEWAY WITH OTHER CONDUCTORS
2. NEED TO PROTECT EXIT SIGN OR BE MOVED