Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROOF DRAINS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2009 | PLUMBING - ROOF DRAINS | Approved | IVRS - Inspection :* OK TO COVER |
|
| 05/28/2009 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* 1. NO TEST ON SYSTEM 2. ABS REQUIRES HANGERS AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. |
|
| 04/28/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* SQUARE TO ROUND CONNECTION MADE OK OK TO POUR SIDEWALK |
|
| 04/24/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* PROVIDE SQUARE TO ROUND CONNECTOR FOR ROOF DRAIN RAIN WATER LEADERS |