Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) OK FOR TILES |
|
| 06/19/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE VERIFICATION OF ACOUSTICAL TREATMENT OF RTU'S AS SHOWN ON M2.1 DETAILS 1 AND 10 2) PROVIDE FULL RADIUS BENDS IN FLEX DUCT OR 90 DEGREE ELBOWS AT REGISTERS AS NEEDED 3) DO NOT SUPPORT DUCT WITH CONDUIT |
|
| 05/18/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/13/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 05/08/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 05/04/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 05/01/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SUSPENDED ROUGH DUCT - OK TO PROCEED 2. SUPPLY & EXHAUST IN HARD LID AREAS OK FOR SHEETROCK EXCEPT ROOMS 121, 122, 123, 114, 115, 124 3. CONDENSATE DRAINS ARE OK 4. DRYER VENTS OK TO COVER |