Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2009 | PLUMBING - MEDICAL GAS/FINAL | Approved | IVRS - Inspection :* | |
| 07/29/2009 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/24/2009 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DOMESTIC WATER STERILIZATION REQUIRED 2) NEED BACKFLOW CERTS 3) FILM PROCESSOR MAY REQUIRE HIGH HAZARD BACKFLOW PROTECTION 4) PROVIDE EQUIPMENT OR LISTING 5) SVBS INSTALLED UPSIDE DOWN, PROVIDE INSTALL INST. 6) LABEL NON POTABLE HOSE BIBS (YELLOW AND BLACK-"NON POTABLE DO NOT DRINK" 7) SECURE DOMESTIC HOSE BIBS 8) SEAL WALL PENETRATIONS 9) EXPOSE MISSING CLEANOUTS 10) CONDENSATE MAY NOT REDUCE IN SIZE AT LAV 11) POINT OF VENT MAY NOT BE BELOW WEIR OF TRAP AT EXTERIOR RP, UNION AND PIPING IS DIRECTLY EMBEDDED IN CONCRETE 12) MISSING #4 TC UNCOVER BELOW GROUND SOV |
|
| 07/02/2009 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/30/2009 | PLUMBING - MEDICAL GAS/FINAL | Not ready for Inspection | IVRS - Inspection :* |