Permit: T08CM00738

Parcel: 12605024B


Addresses:

4020 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - MEDICAL GAS/FINAL

Date Description Inspector Results Comments
07/30/2009 PLUMBING - MEDICAL GAS/FINAL Approved IVRS - Inspection :*
07/29/2009 PLUMBING - MEDICAL GAS/FINAL Not ready for Inspection IVRS - Inspection :*
07/24/2009 PLUMBING - MEDICAL GAS/FINAL Not ready for Inspection IVRS - Inspection :*
1) DOMESTIC WATER STERILIZATION REQUIRED
2) NEED BACKFLOW CERTS
3) FILM PROCESSOR MAY REQUIRE HIGH HAZARD BACKFLOW PROTECTION
4) PROVIDE EQUIPMENT OR LISTING
5) SVBS INSTALLED UPSIDE DOWN, PROVIDE INSTALL INST.
6) LABEL NON POTABLE HOSE BIBS (YELLOW AND BLACK-"NON POTABLE DO NOT DRINK"
7) SECURE DOMESTIC HOSE BIBS
8) SEAL WALL PENETRATIONS
9) EXPOSE MISSING CLEANOUTS
10) CONDENSATE MAY NOT REDUCE IN SIZE AT LAV
11) POINT OF VENT MAY NOT BE BELOW WEIR OF TRAP AT EXTERIOR RP, UNION AND PIPING IS DIRECTLY EMBEDDED IN CONCRETE
12) MISSING #4 TC UNCOVER BELOW GROUND SOV
07/02/2009 PLUMBING - MEDICAL GAS/FINAL Not ready for Inspection IVRS - Inspection :*
06/30/2009 PLUMBING - MEDICAL GAS/FINAL Not ready for Inspection IVRS - Inspection :*