Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T08CM00713
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2008 | FRAMING | Approved | IVRS - Inspection :* | |
05/29/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED SPECIAL INSPECTION REPORTS FOR EPOXY HOLD DOWNS AT STAIRWAY ON STUDS WITH CMSTC16 STRAPS |
|
05/28/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLOCK GARAGE WALLS FOR PERIMETER NAIL AT TOP PLATE FOR GYPSUM SHEAR 2) 3" ON CENTER NAILING PER 508 DETAIL ON SHEAR PANELS 3) CMSTC16 MUST BE 53" PER SHEARPLAN AT STAIRWAY 4) HOLDOWNS ON FULL LENGTH STUDS AT STAIRWAY |
|
05/27/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL OFF SHEATHING PANELS PER 505 DETAIL 2) LOWER BLOCKS IN GARAGE FOR GYPSUM SHEAR PANELS 3) NAIL DBL STUDS TOGETHER THAT HOLDOWNS ARE ON 4) CMSTC16 STRAP ON SAME STUDS AS HOLDOWNS OR OR ENGINEERING IF NOT 5) CMSTC16 STRAP TO SHORT ON STAIRWAY WALL PER PLAN 6) HOLDOWNS UNDER STAIRWAY ON FULL LENGTH STUDS 7) SEAL PAPER EAST WALL NORTH EAST BEDROOM UPSTAIRS 8) MOVE WIRES OFF OF GUSSETS IN GARAGE 9) FILL DWV TEST 10) NAIL PROTECT PLUMBING VENT EAST WALL UPSTAIRS |