Permit: T08CM00709

Parcel: 141350980

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T08CM00709

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/14/2008 EXT METAL CLIPS/EXT SHEATHING Denied 1) CMSTC 16 STRAPS AT STAIRS TO SHORT
2) RETROS STILL NEEDED SOUTHEAST CORNER
3) ANCHOR SILL PLATE PER SHEAR PLAN BETWEEN HOUSE AND GARAGE
4) ANCHOR BOLT NEEDED SOUTH OF FRONT DOOR
5) 2 X 8 BLOCKING NEEDED ABOVE GARAGE OVERHEAD DOOR PER 340 DETAIL
6) BLOCK BETWEEN JACK RAFTERS PER 307 DETAIL
7) RENAIL FLOOR SHEATHING WHERE SHINERS ARE ABOVE OVERHEAD DOOR
8) BLOCK UPSTAIRS DUCTS MINIMUM 3 SIDES
9) STILL CUTTING PENETRATIONS TO EXTERIOR NORTH WALL
10) SEAL PENETRATIONS IN PAPER UNDER STAIRS
11) STOPPED INSPECTION-NOT READY
04/23/2008 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
RETROS NEEDED SOUTHEAST CORNER
04/17/2008 EXT METAL CLIPS/EXT SHEATHING Denied 1) SHEAR PANELS MISSING SOUTH EAST CORNER WITH HOLDOWNS
2) DBL STUD NEEDED UNDER 2 PLY GIRDER IN GREAT ROOM
3) 416 DETAIL MISSED ABOVE FRONT WALL
4) BLOCK SHETHING ABOVE LANDING