Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T08CM00706
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/22/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
07/21/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ITEMS FROM PREVIOUS INSPECTION NOT DONE |
|
07/18/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSULATION INFORMATION POSTED AT PANEL 2) HOUSE ADDESS NEEDED 3) COMBUSTION ARC FAULT BREAKERS NEEDED FOR BEDROOMS AND SMOKE DETECTORS 4) REVERSED POLARITY IN NORTH EAST BEDROOM EAST WALL 5) PRESSURIZE SOLAR WATER HEATER 6) INSULATE DUCT TO FAN UNIT IN ATTIC |