Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T08CM00706
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2008 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
05/15/2008 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* - VERIFY WEST SETBACK PER PREVIOUS INSPECTION - ANCHOR BOLT NEEDED UNDER WINDOW IN GREAT ROOM - ANCHOR BOLTS NEEDED IN FRONT BATHROOM |
|
05/14/2008 | EXCAVATION/LAYOUT REBAR & ZON | Denied | 1) FOUNDATION ANCHORAGE PER SHEAR PLAN ON GARAGE SHEAR WALL (WEST) 2) FOUNDATION ANCHORAGE FOR KITCHEN SHEARWALL 3) SILL PLATE ANCHORAGE FOR SHEARWALL BY FRONT DOOR 4) FILL ALL HOLES IN LTT 20 AT BACK GARAGE SHEARWALL 5) MINIMUM 5 (16D) NAILS IN LEDGER ABOVE FRONT DOOR PER FRAMING PLAN 6) SILL PLATE ANCHORS PER SHEAR PLAN STAIRWAY WALL 7) FIX WEEP SCREED NORTHWEST CORNER OF GARAGE 8) FINISH MESH GARAGE GABLE END 9) SEAL STAPLE PENETRATIONS GARAGE WEST WALL 10) NAIL PROTECT WIRE AT ISLAND 11) OUTSIDE SILL ? LEAKING 12) SUPPORT 3" DRAIN LINE IN GARAGE CEILING 13) NOT READY-STOPPED INSPECTION |
|
03/25/2008 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE 00005 INSPECTION |