Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM00678
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
04/16/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES |
|
04/15/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED SUPPORT WIRES FOR ALL FIXTURES 2. SECURE FIXTURES TO GRID 3. DEMO UN-USED/ABANDONED WIRING 4. SECURE EMT WITHIN 36" OF ENCLOSURES 5. CHECK BOX FILL 6. REMOVE UNUSED RACEWAYS 7. MC TO BE SECURED WITH 12" OF ENCLOSURES 8. WIRE NUTS TO BE USED AS LISTED 9. LOW VOLTAGE TO BE SUPPORTED TO STRUCTURE 10. W.P J-BOX COVER EXTERIOR ENTRY |