Permit: T08CM00678

Parcel: 11207461C


Addresses:

2949 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM00678

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/18/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/16/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES
04/15/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED SUPPORT WIRES FOR ALL FIXTURES
2. SECURE FIXTURES TO GRID
3. DEMO UN-USED/ABANDONED WIRING
4. SECURE EMT WITHIN 36" OF ENCLOSURES
5. CHECK BOX FILL
6. REMOVE UNUSED RACEWAYS
7. MC TO BE SECURED WITH 12" OF ENCLOSURES
8. WIRE NUTS TO BE USED AS LISTED
9. LOW VOLTAGE TO BE SUPPORTED TO STRUCTURE
10. W.P J-BOX COVER EXTERIOR ENTRY