Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM00672
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
04/22/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - PLASTIC CONDENSATE HOSE KINKED - PROVIDE A HOSE CLAMP AT CONNECTION TO COPPER - PROVIDE FUSES IN DISCONNECT ON ROOF - PERMANENTLY I.D CONDENSOR - PROVIDE A SERVICE RECEPTACLE ON ROOF NEAR CONDENSOR |