Permit: T08CM00668

Parcel: 105102520


Addresses:

4282 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/03/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MISSING GUTTER COVER 2ND FLOOR
2. TIGHTEN LOOSE FITTINGS ON ROOF
3. BOXES OVERFILLED
4. LIGHT FIXTURES TO HAVE DISCONNECTS PER 410.75 (G)
11/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CONDUIT FOR LIGHTS
OK CABLE BRACING
OK TEMP POWER SUBJECT TO POSTING OF BOND
11/12/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MANUFACTURES INSTRUCTIONS DO CALL FOR CABLE BRACING

RECEIVED LETTERS OF TORQUE & GFI TESTING
10/24/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROTECT CONDUCTOR 252.46 & 300.4
2. SPLIT BOLT ONLY FOR A RUN & A TAP
3. UFER TO BE CONTINUOUS & AN IRREVERSIBLE SPLICE 250.64
4. MAINTAIN WORKING CLEARANCE SAFE APPROACH
5. PLEASE PROVIDE INSTRUCTIONS TO VERIFY IF CABLE BEARING IS NEEDED
6. NEED LETTER OF TORQUE
7. NO LOADS CONNECTED

* A BOND WILL NEED TO BE POSTED
09/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SUPPORT MC CABLES 12" X 6' - CANS IN SOFFIT

OK AFTER CORRECTIONS