Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00668
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/03/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. MISSING GUTTER COVER 2ND FLOOR 2. TIGHTEN LOOSE FITTINGS ON ROOF 3. BOXES OVERFILLED 4. LIGHT FIXTURES TO HAVE DISCONNECTS PER 410.75 (G) |
|
11/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CONDUIT FOR LIGHTS OK CABLE BRACING OK TEMP POWER SUBJECT TO POSTING OF BOND |
|
11/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. MANUFACTURES INSTRUCTIONS DO CALL FOR CABLE BRACING RECEIVED LETTERS OF TORQUE & GFI TESTING |
|
10/24/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROTECT CONDUCTOR 252.46 & 300.4 2. SPLIT BOLT ONLY FOR A RUN & A TAP 3. UFER TO BE CONTINUOUS & AN IRREVERSIBLE SPLICE 250.64 4. MAINTAIN WORKING CLEARANCE SAFE APPROACH 5. PLEASE PROVIDE INSTRUCTIONS TO VERIFY IF CABLE BEARING IS NEEDED 6. NEED LETTER OF TORQUE 7. NO LOADS CONNECTED * A BOND WILL NEED TO BE POSTED |
|
09/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUPPORT MC CABLES 12" X 6' - CANS IN SOFFIT OK AFTER CORRECTIONS |