Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T08CM00668
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
10/09/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 10-3", 2-4", 2-2" PVC CONTINUATION, 80 FEET OUT |
|
10/02/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK REMAINDER OF 6 - 3" PVC TO TEP X-FMR 2. INSTALL WARNING RIBBON PER NEC 300.5 |
|
06/18/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. NEED TO CONCRETE ENCASE SERVICE SECONDARY RACEWAYS LAST 10' ENTERING BUILDING (MIN. 2" ENCASED), INSTALL WARNING RIBBON DURING BACKFILL OK TO COVER SERVICE SECONDARY TRENCH AFTER CORRECTION |