Permit: T08CM00668

Parcel: 105102520


Addresses:

4282 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
12/09/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
10/09/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 10-3", 2-4", 2-2" PVC CONTINUATION, 80 FEET OUT
10/02/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK REMAINDER OF 6 - 3" PVC TO TEP X-FMR
2. INSTALL WARNING RIBBON PER NEC 300.5
06/18/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. NEED TO CONCRETE ENCASE SERVICE SECONDARY RACEWAYS LAST 10' ENTERING BUILDING (MIN. 2" ENCASED), INSTALL WARNING RIBBON DURING BACKFILL

OK TO COVER SERVICE SECONDARY TRENCH AFTER CORRECTION