Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T08CM00665
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2008 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
10/30/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK MAKE UP IN JUNCTION BOXES AND LIGHT FIXTURES OPENED UP AS REQUESTED BY DAN SANTA CRUZ |
|
10/29/2008 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) CONTR. REQUEST RETURN AFTER HOURS INSP. PAID $150.00 CHECK #15559 2) 1/0 GROUND ELECTRODE CONTRACTOR CALLED OUT ON PLAN, GROUND RODS TO BE DRIVEN ENTIRE LENGTH INTO GROUND PER 250.50 NEC 3) INSTALL INSULATING BUSHINGS ON CONDUIT ENTRIES AS REQUIRED PER 352.46 BLDG STEEL PER 250.10?1 |