Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00665
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/25/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNSCHEDULED ELECTRICAL INSPECTION PERFORMED AT THIS SITE TODAY TO OBSERVE CONST. PROGRESS & POSSIBLE LIGHTING CODE VIOLATIONS. INSPECTOR NOTICED LIGHT FIXTURES INSTALLED UNDER PARKING CANOPIES, WIRED. APPROXIMATELY 3 ROWS WERE OPERABLE VIA TEMP. WIRING TO BREAKER PANEL AT TICKET OFFICE. THIS WAS DONE PRIOR TO ANY INSPECTION APPROVALS. APPROVED PLANS BY "WILDAN" REQUIRE LIGHT FIXTURES TO BE MOUNTED APPROX. 4' FROM CANOPY EDGES TO COMPLY WITH LIGHTING CODE. PLANS CALL OUT LITHONIA #DM232 OR APPROVED EQUAL. THERE IS A HANDWRITTEN NOTE ON PLAN REQUIRING LIGHTS TO BE FULL CUT OFF. THE INSTALLED LIGHT FIXTURES ARE 2-LAMP FLUORESCENT WRAP-AROUND LENS. THE PARKING LOT MANAGER HAS AGREED NOT TO USE LIGHTS UNTIL INSPECTIONS HAVE BEEN APPROVED AND ELECTRICAL CONTR. TO COMPLY WITH ALL NOTES ON PLANS FOR LIGHTING ORDINANCE REQUIREMENTS AND REQUIRED INSPECTIONS. ELEC. CONTR. TO DISCONNECT TEMP. WIRING |