Permit: T08CM00663

Parcel: 13213057A


Addresses:

1031 E BENSON HY


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T08CM00663

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
06/30/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
06/24/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. ROUGH SOIL TEST OK
2. CALL BACK FOR PRE-SLAB
06/23/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. 107, 106, 105, 104, 103, ROUGH SOIL TEST OK UNDERGROUND ONLY
2. #102 & #108 REPAIR LEAK AND RETEST ROUGH SOIL
06/20/2008 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DRAINAGE FITTINGS REQUIRED ON VENTS BELOW
FLOOD LEVEL
2. CORRECT SLOPE
3. TEST ALL NEW PIPING
4. FERNCO COUPLINGS NOT ALLOWED
5. VENTING CLOSET STUB IS NOT PERMITTED PER
SECTIONS 905.3 AND 706.4 SEE CODE AND ANALYSIS ITEM 6
06/16/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. INSTALL PRE-APPROVED PLANS AND UPC 2006
2. DID WALK THRU WITH PLUMBER