Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRING NOT PER PLAN 2. PANEL DIRECTORIES TO BE CORRECT AND RE-PRINTED FOR EXAMPLE - WHERE ARE ("COUNTER RECEPTACLES")? 3. PROVIDE GROUNDING ELECTRODE FOR TTB PER NEC 800.100 4. EXIT SIGN MISSING 5. PROPERLY IDENTIFY HP DISCONNECTS ON ROOF AS TO UNIT AND SPACE # 6. HP1 DISCONNECT DOES NOT HAVE PROPER FRONT WORKING CLEARANCE |
|
| 06/27/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/26/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SEE T07CM04096 |