Permit: T08CM00650

Parcel: 13317064B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/10/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
08/26/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
REMOVE DURA ROCK ON TR WALL
INSTALL TEMP PLUGS IN ALL OPEN PIPES
NOTE: SINKS INSTALLED DRY
APPLY SEALANT PRIOR TO SETTING
07/10/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ISOLATE COPPER FROM METAL AND SECURE
2. INSULATION IS REQUIRED TO BE CONTINUOUS
3. INSTALL BACKING AT MS
4. SAFETY PLATES REQUIRED FOR ALL PIPING WITHIN 1 1/4 OF STUD FACE
07/09/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV W/TEST OK
RECALL FOR PIPE INSULATION AND STRAPPING
07/08/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
COMPLETE TESTING
REDLINE ANY CHANGES OF PIPE ROUTING
WILL NEED TO CAP ANY UNUSED WASTE & VENT FITTINGS
FOR SHELL ABV CEILING
07/07/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO INSULATE AND SECURE WATER PIPING DWN NR