Permit: T08CM00649

Parcel: 13317064B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM00649

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/09/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/03/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CAST IRON 2ND FLOOR IN WALL OK (ONLY)
07/01/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CAST IRON ON TEST ON 2ND FLOOR SOUTH SIDE OK IN WALL
2. PROVIDE APPROVED SUPPORT IN WALLS ON ALL CAST IRON ON 2ND FLOOR SOUTHSIDE
3. INSTALL SANTEE STRAIGHT ON P-6 IN HALLWAY
06/23/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/20/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECT PIPE SLOPE, DOG LEGS AND SAGS
PROVIDE 1/4" PER FOOT
USE A GRADE LEVEL TO ENSURE PROPER INSTALLATION
06/05/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. WATER PIPING SIZING AND PRELIMINARY
PRESSURE TESTS OK
2. ROUTE/AND SUPPORT PIPING IN A MANNER THAT ALLOWS CONTINUOUS PIPE INSULATION PER SPEC.
3. OK TO INSULATE
4. RETEST, SUPPORT AND SECURE PIPING AND RECALL FOR INSPECTION ALONG W/DWV TEST