Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2008 | MECHANICAL - PROGRESS | Approved | IVRS - Inspection :* | |
| 08/29/2008 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* OK TO PROCEED WITH GRID CEILING OK TO CHANGE DUCT LOCATION FOR RTU-2 ALL DUCT SIZES TO REMAIN PER PLAN |
|
| 08/25/2008 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* OK TO WRAP DUCT NO COMBUSTIBLE MATERIALS ALLOWED IN PLENUM CEILING |
|
| 08/15/2008 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* 1. PROVIDE ROUND ELBOWS PER PLANS ADJUSTABLE 90 DEG. NOT ACCEPTABLE 2. SEAL ALL LONG SEAMS IN SNAP LOCK PIPE PER PLANS 3. PROVIDE CONICAL TAPS ON SUPPLY DUCT PER PLANS 4. SEAL ALL "S" AND DRIVE JOINTS 5. VERIFY ACCESS TO DUCT SMOKE DETECTOR PER PLANS 6. COMPLETE EXHAUST SYSTEM INCLUDE SPRING ISOLATORS PER PLANS ON ALL AIR MOVING DEVICES 7. PROVIDE SPIRAL PIPING PER PLANS 8. COMPLETE DUCT SYSTEMS |