Inspection Status: Approved

Inspection History: MECHANICAL - PROGRESS

Date Description Inspector Results Comments
09/25/2008 MECHANICAL - PROGRESS Approved IVRS - Inspection :*
08/29/2008 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
OK TO PROCEED WITH GRID CEILING
OK TO CHANGE DUCT LOCATION FOR RTU-2
ALL DUCT SIZES TO REMAIN PER PLAN
08/25/2008 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
OK TO WRAP DUCT
NO COMBUSTIBLE MATERIALS ALLOWED IN PLENUM CEILING
08/15/2008 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
1. PROVIDE ROUND ELBOWS PER PLANS ADJUSTABLE 90 DEG. NOT ACCEPTABLE
2. SEAL ALL LONG SEAMS IN SNAP LOCK PIPE PER PLANS
3. PROVIDE CONICAL TAPS ON SUPPLY DUCT PER PLANS
4. SEAL ALL "S" AND DRIVE JOINTS
5. VERIFY ACCESS TO DUCT SMOKE DETECTOR PER PLANS
6. COMPLETE EXHAUST SYSTEM INCLUDE SPRING ISOLATORS PER PLANS ON ALL AIR MOVING DEVICES
7. PROVIDE SPIRAL PIPING PER PLANS
8. COMPLETE DUCT SYSTEMS