Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
09/22/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
09/20/2008 ELECTRIC - ABOVE CEILING Partial Approval CONTR. REQUEST SAT. INSP. $150.00 FEE PAID CK#3515

OK EXCEPT HOMERUN J-BOXES, NEED BOX EXTENSIONS, LEAVE TILE BELOW BOXES MENTIONED OFF FOR INSPECTION
09/19/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. SUPPORT OR TIE OFF SUPPORT WIRES FOR CONDUIT OR CABLE AT BOTH ENDS PER 300.11 NEC
2. LV CABLES TO BE SUPPORTED TO A STRUCTURAL MEMBER
SEE NOTES PREVIOUS INSP.
09/15/2008 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*