Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/20/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | CONTR. REQUEST SAT. INSP. $150.00 FEE PAID CK#3515 OK EXCEPT HOMERUN J-BOXES, NEED BOX EXTENSIONS, LEAVE TILE BELOW BOXES MENTIONED OFF FOR INSPECTION |
|
| 09/19/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT OR TIE OFF SUPPORT WIRES FOR CONDUIT OR CABLE AT BOTH ENDS PER 300.11 NEC 2. LV CABLES TO BE SUPPORTED TO A STRUCTURAL MEMBER SEE NOTES PREVIOUS INSP. |
|
| 09/15/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |