Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/11/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CONDENSATE HOSE KINKED AT FAN COIL AND HAS NO SLOPE TO DRAIN TERMINATION I.D. FAN COILS DRAIN LINES NOT SUPPORTED ADEQUATELY INSULATION FALLING OFF EXHAUST DUCTS |
|
| 03/06/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/05/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 03/04/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE CONDENSATE DRAINS AT 2ND FLOOR FAN COILS 2. FINISH WIRING INLINE FANS 3. PROVIDE AIR BALANCE REPORT & DUCT SMOKE DETECTOR TEST |