Permit: T08CM00638

Parcel: 125080820


Addresses:

105 N NORTON AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/05/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
12/03/2008 PLUMBING - FINAL Not ready for Inspection ALL HOSE BIBS REQUIRE AVB's
UNABLE TO LOCATE PLANS, PERMIT AND INSPECTION HISTORY
CONTINUED "NOT READY" MAY RESULT IN REINSPECTION FEE
11/19/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. CLOSET BOND TO BE FLUSH WITH TOP OF CLOSET RING WITH NO FOULING EDGE AND SMOOTH INTERIOR WATER WAY IN RESTROOM #169
2. URINAL VACUUM BREAKER TUB TO HAVE MINIMUM 6" FROM TOP OF URINAL TO CRITICAL LEVEL MARK FOR URINAL FLUSH VALVE IN RESTROOM #173
09/25/2008 PLUMBING - FINAL Partial Approval PARTIAL RESTROOMS #145 & 146, 126 & 139 OK
TEMPERING IS AT WATER HEATER FOR PUBLIC USE LAVS
09/18/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PUBLIC USE LAVS REQUIRE SOME FORM TO CONTROL HOT WATER TEMPERATURE NOT TO EXCEED 110 DEG. BESIDES THE WATER HEATER