Permit: T08CM00638

Parcel: 125080820


Addresses:

105 N NORTON AV


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM00638

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/19/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
11/18/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
RESTROOM 173 OK
169 - PROVIDE APPROVED CLOSET FLANGE INSTALLED CORRECTLY
11/12/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. RESTROOM #173 CLOSET FLANGE OK
2. RESTROOM #169 CLOSET FLANGE TO EXTEND 1/4" ABOVE FINISHED FLOOR
10/20/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ADDITION OF FIXTURE FITTING FOR LAVS OK
WATER DISTRIBUTION OK WHEN ADDITION OF WATER HAMMER ARRESTOR IS INSTALLED, CAN BE SEEN ON FINAL.
10/09/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) THIS INSPECTION FOR 03005 & 03035 DWV ONLY
2) WATER TEST PER RED LINE ON MENS RESTROOM #173
3) ADDITION OF MOP SINK REQUIRES REVISED CITY APPROVED PLAN
4) PROVIDE DBL FIXTURE FITTING FOR BACK TO BACK LAVS
10/07/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RESTROOM #208 & #165 CLOSET FLANGE OK
09/25/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CAPS FOR SINK AT 219 OK
09/18/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGE OK RESTROOM 145, 139, 126
08/26/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGES IN 146 OK
145 NEEDS SMOOTH INTERIOR WATER WAY & FLANGE TO BE ON TOP OF TILE SURFACE. SHOWER DRAINS DEMO ROOM BACK TO BACK 139 & 126 OK
08/25/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE CAPS ON EXISTING SHOWERS #138 BACK TO BACK
2. RECALL ALL CLOSET FLANGES FOR INSPECTION
3. PROVIDE ACCESS TO EXISTING TRAP PRIMERS
AND 3/4" SHUT OFF VALVE IN ROOM 139

NOTE: ALL FIXTURES (KITCHEN) REPLACEMENTS REQUIRE CORRECT DRAINAGE FITTINGS. PUBLIC USE LAVS REQUIRE HOT WATER TO BE 110 DEG. WITH WATER HEATER NOT BEING SOLE CONTROL OF THIS TEMPERATURE
08/19/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SEE NOTE #2 FROM 8/6/08 - CONCRETE POURED W/O INSPECTION
2. INTERMEDIATE NOT READY - NO TEST ON ABS
CONTINUED "NOT READY" WILL RESULT IN REINSPECTION FEE
07/09/2008 PLUMBING - INTERMEDIATE Not ready for Inspection CLOSET FLANGES TO EXTEND 1/4" ABOVE FINISHED FLOOR
06/18/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO COVER WALLS
SUPPORTS ADDED AS REQUIRED
2. NEED TO RECHECK CLOSET FLANGES AFTER FLOOR IS SET