Permit: T08CM00638

Parcel: 125080820


Addresses:

105 N NORTON AV

Inspection Status: Approved

Inspection History: PLUMBING - PRE SLAB

Date Description Inspector Results Comments
08/25/2008 PLUMBING - PRE SLAB Approved IVRS - Inspection :*
08/21/2008 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
08/06/2008 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
1) OK TO COVER UNDERGROUND AT #126, 139 AB'S WATER TEST OK
2) RECALL 03015 FOR PRE SLAB
08/04/2008 PLUMBING - PRE SLAB Not ready for Inspection 1. AT #145 & #146 - CLOSETS SET BEFORE FLANGE APPROVAL
NOTE: REQUIRE 18" CLEAR IN FRONT OF CLEAN OUT
2. AT 126 & 139 - HORIZONTAL VENTING BELOW FLOOD RIM LIMITED TO STRUCTURAL CONDITIONS
3. EXPOSE ALL FITTINGS UNDERGROUND
REQUIRE DRAINAGE FITTINGS AT URINAL - COPPER NOT SUPPORTED - NO TEST ON LAVS
06/10/2008 PLUMBING - PRE SLAB Partial Approval IVRS - Inspection :*
1. CORRECTIONS MADE OK
OK FOR CONCRETE
2. NOTE: 3" CLEANOUTS REQUIRE 18" OF CLEARANCE
IN FRONT
3. THIS INSPECTION FOR ROOMS #145 & #146
05/28/2008 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*
PROVIDE LISTING FOR REPAIR COUPLINGS UNDER SLAB
NO PIPE WRAPS
05/15/2008 PLUMBING - PRE SLAB Not ready for Inspection IVRS - Inspection :*