Permit: T08CM00633

Parcel: 12801005H

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/16/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/14/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE FUSES IN FAN COIL DISCONNECT
SECONDARY DRAIN PAN MUST BE 1 1/2" LARGER ON ALL SIDES OF UNIT
10/10/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. CONDENSOR NOT FUSED CORRECTLY.
2. PERMANENTLY I.D EQUIPMENT ON ROOF
3. REPAIR REFER LINE INSULATION
4. PROVIDE BUSHINGS AT FAN COIL
5. MARK UNIT DATA PLATE ON FAN COIL & FUSE ACCORDINGLY
6. PROVIDE SECONDARY DRAIN PAN
7. PROVIDE AIR BALANCE
8. NEED TO TEST DUCT SMOKE DETECTORS