Inspection History: MECHANICAL - FINAL
Permit Number - T08CM00633
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
10/14/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE FUSES IN FAN COIL DISCONNECT SECONDARY DRAIN PAN MUST BE 1 1/2" LARGER ON ALL SIDES OF UNIT |
|
10/10/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. CONDENSOR NOT FUSED CORRECTLY. 2. PERMANENTLY I.D EQUIPMENT ON ROOF 3. REPAIR REFER LINE INSULATION 4. PROVIDE BUSHINGS AT FAN COIL 5. MARK UNIT DATA PLATE ON FAN COIL & FUSE ACCORDINGLY 6. PROVIDE SECONDARY DRAIN PAN 7. PROVIDE AIR BALANCE 8. NEED TO TEST DUCT SMOKE DETECTORS |