Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T08CM00633
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
09/12/2008 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. GEC TO BOND TO BOTH ENDS OF RACEWAY 2. GEC TO TERMINATE @ XO TRY NOT TO STACK LUGS 3. BONDING JUMPER TO BE SAME SIZE AS GEC 4. INSTALL PROTECTIVE BUSHING |