Permit: T08CM00630

Parcel: 129063280


Addresses:

2731 E 21ST ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
04/17/2008 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*
04/16/2008 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UNABLE TO LOCATE GROUND RODS
2) BOND GAS AND WATER TO NEW PANEL
3) YOU HAVE NO CLAMP ATTACHING THE RISER TO THE BLDG
4) RAISE ATTACHMENT (WIRE) CLAMP TO UNDERSIDE OF MINERALAC CLAMP TO PREVENT MINERALAC CLAMP FROM SLIPPING DOWN RISER