Permit: T08CM00618

Parcel: 130090910


Addresses:

3341 E 28TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
03/04/2008 ELECTRIC - UNDERGROUND Approved
02/29/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) DO NOT PARRALLEL GROUNDING ELECTRODE CONDUCTORS
2) GAS BOND CONDUCTOR TO BE GREEN OR BARE ENTIRE LENGTH, ALSO WATER BOND
3) USE CORRECT COLOR CONDUCTORS FOR UNGROUNDED (HOT) CONDUCTORS
4) NEUTRAL CONDUCTOR TO BE WHITE ENTIRE LENGTH IN RACEWAY
5) RECEIVED MONEY ORDER #100765597878 FOR $150.00
02/26/2008 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*